Reader wiring: Wiegand and OSDP
Match reader conductors to controller terminals for Wiegand and OSDP (RS-485) readers.
Simulation — not real hardware
Simulation — not real hardware. Results are planning estimates from the formulas shown; real equipment, cabling and firmware differ. Check datasheets and site conditions before you buy or install.
What this lab covers
Most card readers on Indian sites still use Wiegand: two data lines (D0 and D1) pulsed by the reader, plus power, ground and lines the controller uses to drive the reader's LED and buzzer. OSDP replaces the data lines with an RS-485 pair, so the controller and reader talk both ways, the link can be encrypted and a missing reader is noticed.
Colours below follow a common convention. They are not a standard every maker follows — the reader's datasheet and the controller's terminal labels always decide.
Worked example
A Wiegand reader's green conductor goes to D0 and white to D1. Swap them and most controllers read a different card number (or none) — a classic "card not recognised" fault on a new install.
For OSDP, power the reader from the controller (or a local supply sharing a ground), take A and B on a twisted pair, and set the reader's address and baud rate to match the controller.