Power budgeting
PoE classes against a switch budget, battery backup hours and a fire panel standby battery.
Simulation — not real hardware
Simulation — not real hardware. Results are planning estimates from the formulas shown; real equipment, cabling and firmware differ. Check datasheets and site conditions before you buy or install.
What this lab covers
Three power questions come up on every security job. Will the PoE switch power every camera — by the class each announces and by what it really draws? How long will a battery bank carry the load when mains fails? And how big must a fire alarm panel's standby batteries be?
Battery hours here are bank watt-hours × usable depth of discharge × converter efficiency ÷ load. Lead-acid capacity also falls in heat and with age, so leave margin. For fire alarm batteries use the method in the standard your project follows (for example IS 2189 or BS 5839-1) and the panel maker's calculation; the common method shown multiplies by an ageing factor of 1.25.
Worked example
Two 12 V 7 Ah batteries in series = 24 V 7 Ah = 168 Wh. At 80 % depth of discharge and 85 % efficiency, a 20 W load runs about 5.7 hours.
Fire panel: 0.25 A × 24 h standby + 1.5 A × 0.5 h alarm = 6.75 Ah; × 1.25 = 8.44 Ah, so the next standard size up.